VisuKit

SvelteKit-native OPC UA visualization — live tags, trends, and a historian.

VisuKit connects to one or more OPC UA servers (a Siemens S7-1500, PLCSIM Advanced, or any other server), subscribes to the tags you declare in a single JSON file, and gives you:

  • a live HMI page that auto-builds itself from the tag catalog — gauges, LEDs, value readouts, setpoint inputs, and command buttons picked automatically from each tag's shape
  • a multi-pen trend view (uPlot on canvas — fast) that stitches historical data and the live stream into one seamless chart
  • a SQLite historian for the tags you flag, with a downsampling read API
  • a write path for setpoints and boolean commands, routed to the right server

No database server, no broker, no cloud. Two Node processes and a JSON file.

Quickstart — no PLC required

Requires Node.js ≥ 24. Three terminals:

npm install

npm run sim        # 1. simulated S7-1500 OPC UA server (opc.tcp://localhost:4840)
npm run gateway    # 2. the gateway: OPC UA → WebSocket (:4900) + historian
npm run dev        # 3. the web app → http://localhost:5173

Open http://localhost:5173 — you'll see two simulated machines with live values. Change a setpoint or hit Turn on, and watch the write go to the (simulated) PLC and the confirmed value come back. The Trends page fills up as the historian collects samples.

Architecture

                    ┌──────────────────────── gateway (Node, singleton) ───────────────┐
 OPC UA server(s)   │  client.ts      one session + subscription per server            │
 (PLC / PLCSIM /    │─►                                                                │
  npm run sim)      │  historian.ts   SQLite (node:sqlite), tags flagged `log`         │
                    │  wsServer.ts    WebSocket :4900 — catalog, snapshot, deltas,     │
                    └─────────────────writes ─────────────────┬────────────────────────┘
                                                              │
                    ┌──────────────────── SvelteKit app ──────▼────────────────────────┐
                    │  liveStore.svelte.ts   reactive mirror of the WS stream          │
                    │  /            live HMI, auto-built from the tag catalog          │
                    │  /trends      multi-pen trend (history API + live stream)        │
                    │  /api/history downsampled series from the historian SQLite       │
                    └───────────────────────────────────────────────────────────────────┘

The gateway is deliberately its own process: it holds exactly one OPC UA session per server no matter how many browser tabs connect, and it keeps collecting history while the web app restarts during development.

Configuration — config/tags.json

One file defines everything: which servers to connect to, and which tags to subscribe to.

{
	"servers": {
		"sim-plc": "opc.tcp://localhost:4840/UA/VisuKitSim"
		// or with credentials: "plc2": { "endpoint": "opc.tcp://…", "user": "…", "pass": "…" }
		// or encrypted:  "plc3": { "endpoint": "opc.tcp://…", "security": "SignAndEncrypt" }
		//   security: None (default) | Sign | SignAndEncrypt
		//   securityPolicy: Basic256Sha256 (default) | Aes128_Sha256_RsaOaep | Aes256_Sha256_RsaPss
	},
	"tags": [
		{
			"id": "machine1.temp", // unique key used everywhere (WS stream, components, historian)
			"label": "Temperature",
			"nodeId": "ns=3;s=\"MachineDB\".\"Machine1\".\"Temperature\"",
			"server": "sim-plc",
			"dataType": "Double", // Double | Float | Int32 | Boolean | String
			"unit": "°C",
			"group": "Machine 1", // display grouping on the HMI
			"log": true, // historize to SQLite
			"min": 0,
			"max": 120, // range hints → renders as a gauge
			"decimals": 1
		}
	]
}

How the HMI picks a component for each tag:

Tag shape Component
writable Boolean command button
writable numeric setpoint input
Boolean LED
numeric with min+max radial gauge
anything else value readout

Pointing it at a real PLC

  1. Find your NodeIds: npm run probe -- opc.tcp://<plc-ip>:4840 walks the address space and prints every variable's NodeId, type, and value.
  2. Put them in config/tags.json. S7-1500 note: PLC data lives in the PLC's own namespace (usually ns=3) with string NodeIds like ns=3;s="MyDB"."MyTag" — the quotes are part of the string. An S7 Real is a 4-byte Float (not Double) — this matters for writes.
  3. Restart the gateway.

For Siemens: activate the OPC UA server in the CPU properties (TIA Portal) and download the hardware config — port 102 being open does not mean OPC UA (port 4840) is on. With PLCSIM Advanced, use the PLCSIM Virtual Eth. Adapter <Local> mode; no physical network needed.

Security & certificates

By default connections use security None + anonymous — fine for first bring-up and simulators, but don't run an unencrypted PLC connection across an untrusted network. For real plants, turn on certificate-based encryption per server:

"plc1": { "endpoint": "opc.tcp://…", "security": "SignAndEncrypt" }

(Policy defaults to Basic256Sha256 — the right choice for S7-1500.) On first secure start the gateway creates its own certificate under data/pki/ (pure JS — no OpenSSL, no admin rights) and prints its path. OPC UA trust is two-way:

  1. The server must trust the gateway. Import data/pki/own/certs/visukit-gateway.pem into the server's trust list. TIA Portal: CPU properties → OPC UA → Server → Security → Secure channel → trusted clients (needs the project's certificate manager under Global security settings), then download. For bring-up you can instead enable "Automatically accept client certificates during runtime" — tighten it later.
  2. The gateway must trust the server. Default is trust-on-first-use: the server's cert is accepted on first connect and pinned in data/pki/trusted/certs/ (changes are then rejected). For strict onboarding set OPCUA_STRICT_CERTS=1 — unknown server certs are rejected into data/pki/rejected/; move the file to data/pki/trusted/certs/ and restart the gateway to trust it.

The bundled sim also serves Sign/SignAndEncrypt endpoints (auto-accepting client certs), so you can rehearse the whole exchange without a PLC: OPCUA_SECURITY=SignAndEncrypt npm run gateway.

Environment variables (all optional)

Variable Default What it does
TAGS_CONFIG config/tags.json path to the config file
GATEWAY_WS_PORT 4900 gateway WebSocket port
HISTORIAN_DB data/historian.sqlite historian SQLite file
OPCUA_ENDPOINT override the endpoint (single-server config)
OPCUA_USER/PASS credentials (single-server config)
OPCUA_SECURITY override security mode (single-server config)
OPCUA_SECURITY_POLICY override security policy (single-server config)
OPCUA_PKI_ROOT data/pki gateway certificate store
OPCUA_STRICT_CERTS 1 = reject unknown server certs (no TOFU)
PUBLIC_GATEWAY_WS ws://<host>:4900 WS URL the browser connects to
SIM_PORT 4840 sim server port

Deployment

npm run build emits a self-contained Node app in ./build (adapter-node); run it with node build (set PORT/ORIGIN). Run the gateway (npm run gateway) alongside it under your process manager of choice (pm2, NSSM, systemd).

License

MIT